- installation
- mobile
- RoHS
- REACH
- CE
Application / Description
Measuring-, signal, control-, and regulation technology as well as call plants and data processing. High flexibility and small outside diameter characterise this cable.
Variant data
O.D.
- approx. 4,40 mm
weight
- 35,0 kg/km
Cu-weigth
- 9,6 kg/km
skinning tool (jacket)
- 20100
skinning tool (core)
- 20310 / 30900
Construction / data
Conductor
- bare stranded copper wire
Structure of conductor
- 14x0,15 mm
Cross section
- 0,25 qmm
Core-Ø
- approx. 1,30 mm
number of cores
- 4
Core insulation
- PVC acc. to VDE 0207
Colour sequence
Twisting
- cores in layers
Outer jacket
- PVC acc. to VDE 0207
Outer jacket colour
- grey sim. RAL 7001
Dimension
- 4 x 0,25 qmm
Technical characteristics
Not allowed for high current applications!Temperature range
- static: -30 °C to +70 °C
- dynamic: -5 °C to +70 °C
Bending radius
- > 15 x O.D.
Operating capacity (C/C)
- approx. 120 pF/m
Operating voltage
- 900 V
Testing voltage
- 2.500 V
Current capacity (at +25° C)
- 2,50 A (by respectively one core per cabel is loaded)
Insulation resistance
- > 200 MOhm x km at + 20°C
Conductor resistance
- max. 77,8 Ohm/km
Packaging
Rings at 100m, ReelsLower and upper lengths according to availability. Special packaging on request.